Z+ ELECTRICAL WIRE
These are eco-friendly wires which are made of multi draw Pure Copper Conductors. Purity of copper offers uniform resistance which makes these wires long lasting. "Z+" this value itself suggests that it is flame retardant and Halogen free compound which gives better insulation & Electrical Properties.
Application
Wiring in all installations where fire safety is more important. Schools, theaters, commercial complexes, air conditioned apartments, high rise buildings, fire alarm and emergency lighting circuits, electronic and computerized installations, modern offices depending heavily on electronic data preservation etc.
FLEXIBLE (Temperature upto 90 C) (Z+) | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Nominal cross sectional area of conductor | Nos & Diameter of Wires | Nominal thickness of insulation | Approx. Overall Diameter of Wire | Current rating 2 cable single phase ac/dc | Max DC Resistance at 20 Deg. C | ||||||
sq. mm | mm | mm | mm | Amps | ohm/km | ||||||
1 | 14/0.3 | 0.7 | 2.8 | 13 | 18.1 | ||||||
1.5 | 22/0.3 | 0.7 | 3.1 | 16 | 12.1 | ||||||
2.5 | 36/0.3 | 0.8 | 3.8 | 22 | 7.41 | ||||||
4 | 56/0.3 | 0.8 | 4.4 | 30 | 4.61 | ||||||
6 | 84/0.3 | 0.8 | 5.1 | 38 | 3.08 | ||||||
10 | 140/0.3 | 6 | 6 | 1.91 | 1.91 | ||||||
FLEXIBLE (Temperature upto 125 C) (Z+ Thermo Setting) | |||||||||||
sq. mm | mm | mm | mm | Amps | ohm/km | ||||||
1 | 14/0.3 | 0.7 | 2.8 | 13 | 18.1 | ||||||
1.5 | 22/0.3 | 0.7 | 3.1 | 16 | 12.1 | ||||||
2.5 | 36/0.3 | 0.8 | 3.8 | 22 | 7.41 | ||||||
4 | 56/0.3 | 0.8 | 4.4 | 30 | 4.61 | ||||||
6 | 84/0.3 | 0.8 | 5.1 | 38 | 3.08 | ||||||
10 | 140/0.3 | 1 | 6 | 51 | 1.91 |
A brief comparison of PVC and Z+ Cables is given below. | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Properties | PVC | Z+ | ||||||||||||
Halogen Gas (mg/g) | >200 | < 0.5 | ||||||||||||
Corrosive gas (pH) | 2-Jan | 6 | ||||||||||||
Smoke Density (Rating) | >70 | <20 | ||||||||||||
0 Usage Temperature (C) | 70 | 90 | ||||||||||||
0 Low Temperature (C) | -20 | -50 | ||||||||||||
Dioxin | YES | NO | ||||||||||||
Toxic Halogen Gas | YES | NO | ||||||||||||
Lead | YES | NO |